Emerson 1F75P-21NP Thermostat Operation Manual
The Emerson 1F75P-21NP is a non-programmable thermostat designed for single-stage cooling and one or two stage heating systems, suitable for electric-only systems with auxiliary heat. It features a clear backlit display, simple operation, and precise temperature control. Below are the key specifications and operation instructions.
Key Specifications
- Type: Non-programmable thermostat for single-stage cooling and one or two stage heating
- Compatibility:
- Electric-only systems
- One-stage auxiliary heat
- Not compatible with systems exceeding 30 VAC
- Power Source:
- Battery: 20 to 30 VAC, NEC Class II, 50/60 Hz (2 AA alkaline batteries, Duracell or Energizer recommended)
- Hardwired: 20 to 30 VAC, NEC Class II, 50/60 Hz with common (C) wire
- Electrical Rating:
- Terminal Load: 1.5 A per terminal, 2.5 A maximum all terminals combined
- Rated Differentials (@ 6°F/Hr): Heat Pump (Heating): 0.9°F (Fast), 1.2°F (Med), 1.7°F (Slow); Heat Pump (Cooling): 0.9°F (Fast), 1.2°F (Med), 1.7°F (Slow); Auxiliary Heat: 0.5°F (Fast), 0.75°F (Med), 1.9°F (Slow)
- Setpoint Range: 60°F to 85°F (16°C to 29°C)
- Display: Backlit LCD display, adjustable ±5°F
- Operating Conditions:
- Ambient: 32°F to 105°F (0°C to 41°C)
- Humidity: 90% non-condensing max
- Shipping: -20°F to 150°F (-29°C to 65°C)
- Dimensions: 3-3/4” H x 6” W x 1-1/8” D
- Features:
- Backlit display with large, easy-to-read temperature
- Adjustable temperature display calibration
- Compressor protection (up to 5-minute delay)
- Keypad lockout option
- Thermostat Configuration Options:
- Single Stage Cooling, One or Two Stage Heating – 1 Stage Aux Heat
- Electric-only systems
- Maximum Stages Heat/Cool: 2/1
Operation Instructions
Initial Setup
1. Insert Batteries: Install 2 AA alkaline batteries in the rear compartment, removing the battery tag to activate. Replace when the battery indicator shows low (approximately every 2 years).
2. Power On: If hardwired, ensure 20-30 VAC is supplied via the C terminal. The display should show the home screen.
3. Configure System:
- Press and hold MENU for 8 seconds to access INSTALLER MENU.
- Select system type (Heat Pump or Conventional), heat cycle rate (Fast, Medium, Slow), and compressor delay (item 50).
- Exit by pressing RUN or waiting for the display to return to normal.
Operating the Thermostat
1. Select Mode: Press SYSTEM to choose HEAT, COOL, AUTO, AUX (for heat pumps), or OFF.
2. Adjust Temperature: Press up/down arrows to set the desired temperature.
3. Fan Control: Press FAN to select AUTO (runs with heating/cooling) or ON (continuous).
4. Verify Operation:
- In HEAT mode, set temperature 1°F above room temperature; “Heat On” should display, and the system should start.
- In COOL mode, set temperature 1°F below room temperature; “Cool On” should display after up to a 5-minute compressor delay.
- In AUX mode, set temperature 3°F above room temperature; “Heat On Auxiliary” should display, and auxiliary heat should start.
Temperature Display Adjustment
1. Press MENU to access USER MENU.
2. Use NEXT to navigate to Thermometer Adjustment (item 07).
3. Press up/down arrows to adjust the displayed temperature by ±5°F to match the actual room temperature.
4. Press RUN to save and exit.
Note: Use a separate thermometer for calibration. Relocate the thermostat if near drafts or heat sources.
Troubleshooting
- No Display: Check battery polarity or replace batteries. Verify C wire connection for hardwired setups. Reset by removing batteries for 2 minutes.
- No Heat/Cool: Ensure SYSTEM is set to HEAT/COOL/AUX, setpoint is above/below room temperature, and circuit breaker is on. Check for compressor delay (up to 5 minutes). Verify wiring and system settings.
- Furnace Cycles Too Often: In INSTALLER MENU, adjust heat cycle rate to MEDIUM or SLOW to reduce cycling frequency.
- Inaccurate Temperature: Calibrate in USER MENU (item 07). Ensure thermostat is placed about 1.5 meters above the floor, away from drafts, heat sources, or exterior walls.
- Blank Display After Battery Replacement: Remove thermostat from base, wait 30 seconds, and reattach. Check wiring for loose connections.
- Room Temperature Rises in Cooling Mode: Verify the outdoor unit is running and not obstructed. Check filters, vents, and ductwork for blockages. Ensure SYSTEM is set to COOL, not HEAT.
Installation Instructions
Warning: Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code. Disconnect power at the main fuse or circuit breaker before installation to prevent electrical shock or equipment damage.
Remove Old Thermostat
- Before removing wires, mark wires for terminal identification to ensure proper connections to the new thermostat.
Installing New Thermostat
- Pull the thermostat body off the thermostat base. Do not force or pry to avoid damage.
- Place base over the hole in the wall and mark mounting hole locations using the base as a template.
- Move base out of the way, drill mounting holes. Use plastic screw anchors if existing holes are too large.
- Fasten base snugly to the wall using mounting holes and two mounting screws. Leveling is for appearance only and does not affect operation.
- Connect wires to the terminal block on the base using the appropriate wiring schematic.
- Push excess wire into the wall and plug the hole with fire-resistant material (e.g., fiberglass insulation) to prevent drafts.
- Carefully line the thermostat up with the base and snap into place.
Battery Location
- Includes 2 AA alkaline batteries at the factory with a battery tag to prevent power drainage. Remove the tag to engage batteries.
- To replace, set system to OFF, remove thermostat from the wall, and install batteries in the rear along the top. Use premium brand AA alkaline batteries like Duracell or Energizer.
- If the home will be unoccupied for over 3 months and the battery level indicator shows low, replace batteries before leaving.
Power Stealing Switches
Leave switches in the "On" position for most systems. Details in the following table:
Thermostat Power Method | Switch Position/Description |
Battery Powered, no 24 Volt system | Switches "On", thermostat runs on batteries. |
Hardwired with Battery Back-up, for 24 Volt systems with common connection from transformer to "C" terminal | Switches "On", thermostat runs on power directly from transformer with battery back-up. |
Battery Powered with Power Stealing Assist, for 24 Volt systems with no common connection | Switches "On", thermostat runs on batteries and supplemental power drawn through heat or cool circuit. |
Caution: Power Stealing Assist may cause issues on systems with high impedance electronic modules (e.g., furnace draft inducer motor running with no call for heat, furnace fan not turning off). If incompatible, set switches to "Off" to operate on batteries.
Emerson Thermostat Manual© - All Rights Reserved 2025