Emerson 1F78-151 Thermostat Operation Manual
The Emerson 1F78-151 is a 5+2 day programmable, single-stage thermostat designed for conventional gas, oil, electric, or millivolt systems, as well as heat pump systems without auxiliary heat. It features a backlit digital display, easy programming, and energy-saving settings for efficient temperature control. Below are the key specifications and operation instructions.
Key Specifications
- Type: Programmable (5+2 day), single-stage thermostat
- Compatibility:
- Conventional systems (gas, oil, electric, millivolt, 24V)
- Heat pump systems without auxiliary heat
- Heat only, cool only, or heat/cool systems
- Not compatible with multi-stage systems, electric baseboard heat, or systems exceeding 30 VAC
- Power Source:
- Battery: 2 AAA alkaline batteries (Duracell or Energizer recommended)
- Hardwired: 20-30 VAC, NEC Class II, 50/60 Hz with common (C) wire (optional)
- Electrical Rating:
- Terminal Load: 0.05 to 1.5 A per terminal, 1.5 A max combined
- Rated Differentials: Heat (0.6°F to 1.9°F, adjustable), Cool (1.2°F)
- Setpoint Range: 45°F to 90°F (7°C to 32°C)
- Display: Backlit digital LCD display (backlight off by default, activated by pressing TIME and RUN simultaneously)
- Operating Conditions:
- Ambient: 32°F to 105°F (0°C to 41°C)
- Humidity: 90% non-condensing max
- Shipping: -4°F to 150°F (-20°C to 65°C)
- Dimensions: 3-13/16” H x 5-1/8” W x 1-1/8” D
- Features:
- 5+2 day programming (Mon-Fri, Sat-Sun) with 4 time/temperature settings per day
- Backlit display for low-light conditions
- Filter change indicator (0 to 1950 hours, adjustable)
- Automatic heat/cool changeover
- Temporary temperature override
- Compressor protection (up to 5-minute delay)
- Wall plate (F61-2550, 6.5” W x 4.5” H) to cover marks from previous thermostats
- Selectable Celsius or Fahrenheit display
- Thermostat Configuration Options:
- Conventional Gas, Oil, Electric (mV and 24V), Heat Only, Cool Only, or Heat/Cool Systems - Maximum Stages Heat/Cool: 1/1
- Heat Pump (Air Source or Geothermal) without Aux. Heat - Maximum Stages Heat/Cool: 1/1
Operation Instructions
Initial Setup
1. Insert Batteries: Install 2 AAA alkaline batteries in the rear compartment, removing the battery tag to activate. Replace when “LO BATTERY” appears (approximately every 2 years).
2. Power On: If hardwired, ensure 20-30 VAC is supplied via the C terminal (optional). The display should show the home screen.
3. Configure System:
- Locate the GAS/ELECTRIC switch on the back of the thermostat (default: GAS). Set to ELECTRIC for systems requiring the thermostat to control the fan during heating (e.g., electric heat or heat pumps).
- Access CONFIGURATION MENU by pressing SYSTEM to OFF, then holding up/down arrows for 5 seconds.
- Configure options:
- Item 1: Select heat pump or conventional system.
- Item 2: Select O (cool) or B (heat) for heat pump changeover valve.
- Item 3: Temperature display (°F or °C).
- Item 5: Filter change reminder (0 to 1950 hours, 0 to disable).
- Exit by pressing RUN or waiting for the display to return to normal.
Setting the Clock and Day
1. Press TIME button.
2. Use up/down arrows to adjust hours, minutes, and AM/PM.
3. Press TIME again to set the day of the week, using up/down arrows to select.
4. Press RUN to save and exit.
Operating in Non-Programmable Mode
1. Select Mode: Press SYSTEM to choose HEAT, COOL, AUTO, or OFF.
2. Adjust Temperature: Press up/down arrows to set the desired temperature.
3. Fan Control: Press FAN to select AUTO (runs with heating/cooling) or ON (continuous).
4. Manual Operation: Press HOLD to maintain a constant temperature, bypassing the programmed schedule. Press RUN to resume programming.
Operating in Programmable Mode
1. Factory Schedule: Pre-programmed with energy-saving settings (e.g., Heat: 70°F day, 62°F night; Cool: 78°F day, 82°F night). Press RUN to use defaults.
2. Custom Schedule:
- Press PRGM, then select HEAT or COOL.
- Choose weekday (Mon-Fri) or weekend (Sat-Sun) programming.
- Set times/temperatures for Wake, Leave, Return, and Sleep periods using TIME and up/down arrows.
- Save by pressing RUN.
3.
Temporary Override: Press up/down arrows to adjust temperature; it holds until the next programmed period.
4.
Permanent Hold: Press HOLD to maintain a set temperature until RUN is pressed.
5.
Disable Programming: In CONFIGURATION MENU, set programming to non-programmable mode if desired.
Advanced Features
1. Filter Change Reminder: Alerts when filter replacement is needed (set in CONFIGURATION MENU, Item 5). Reset by pressing up/down arrows simultaneously in CONFIGURATION MENU.
2. Compressor Protection: Automatically delays compressor restart (up to 5 minutes) to prevent damage, indicated by a flashing snowflake icon.
3. Backlight Activation: Press TIME and RUN simultaneously to enable/disable the backlight for low-light conditions.
Troubleshooting
- No Display: Check battery polarity or replace batteries. Verify C wire connection for hardwired setups. Reset by pressing up/down arrows and moving SYSTEM switch from OFF to HEAT simultaneously.
- No Heat/Cool: Ensure SYSTEM is set to HEAT/COOL, setpoint is above/below room temperature, and circuit breaker is on. Check for compressor delay (up to 5 minutes, indicated by flashing snowflake icon). Verify wiring connections.
- Fan Runs Continuously: Set FAN to AUTO. Ensure SYSTEM is not in AUTO mode if only heating or cooling is desired.
- Inaccurate Temperature: Calibrate in CONFIGURATION MENU (Item 4). Ensure thermostat is not near drafts, heat sources, or exterior walls.
- “FILTER” Displayed: Indicates filter replacement needed. Clear by pressing up/down arrows in CONFIGURATION MENU (Item 5).
- Erratic Operation: Reset by pressing up/down arrows and moving SYSTEM switch from OFF to HEAT. If the thermostat remains stuck (e.g., fixed at 62°F heat or 85°F cool), perform a reset.
Installation Instructions
Warning: Thermostat installation and all components shall conform to Class II circuits per the NEC code. Do not use with line voltage systems; verify wiring with a qualified technician if unsure.
Remove Old Thermostat
- Turn off power at the main fuse or circuit breaker until installation is complete.
- Remove the front cover of the old thermostat. With wires attached, remove the wall plate. If it has a mounting plate, remove the thermostat and plate as an assembly.
- Mark wires for terminal identification using labels provided with the new thermostat.
- Disconnect wires one at a time, ensuring they do not fall back into the wall.
Installing New Thermostat
- Gently pull the thermostat cover off the base. Do not force or pry to avoid damage.
- Place base over the hole in the wall and mark mounting hole locations using the base as a template.
- Move base out of the way and drill mounting holes. Use plastic screw anchors if existing holes are too large.
- Fasten base snugly to the wall using two mounting screws. Leveling is for appearance only and does not affect operation.
- Connect wires to the terminal block using the appropriate wiring schematic (see Wiring section).
- Push excess wire into the wall and plug the hole with fire-resistant material (e.g., fiberglass insulation) to prevent drafts.
- Snap the thermostat onto the base carefully.
Battery Location
- Includes 2 AAA alkaline batteries with a battery tag to prevent power drainage. Remove the tag to engage batteries.
- Replace batteries when “LO BATTERY” appears or before leaving the home unoccupied for over 3 months. Use premium brand AAA alkaline batteries (e.g., Duracell or Energizer).
- Install batteries along the top of the rear compartment, ensuring positive (+) ends are oriented correctly.
Wiring and Terminal Functions
Refer to the equipment manufacturer’s instructions for specific wiring. The following table describes typical terminal functions:
Terminal | Function |
RC | Cooling power (24 VAC) |
RH | Heating power (24 VAC) |
C | Common wire for 24 VAC power from transformer (optional for battery operation) |
W | Heat relay |
Y | Compressor contactor (cooling) |
G | Fan relay |
O | Heat pump changeover valve (energized in cooling) |
B | Heat pump changeover valve (energized in heating) |
Note: For two-wire heat-only systems, connect one wire to RH and the other to W. For single-transformer systems, jumper RC and RH. For heat pumps, set O/B switch to “O” (cool) or “B” (heat) as required by the system. The thermostat can operate on battery power if no C wire is available. Do not exceed specified voltage ratings.