Emerson 1F83C-11NP Thermostat Operation Manual

The Emerson 1F83C-11NP is a non-programmable, single-stage thermostat designed for conventional gas, oil, electric, or heat pump systems with no auxiliary heat. It features a clear backlit display, simple operation, and precise temperature control. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Operating the Thermostat 2.3. Temperature Display Adjustment 2.4. Troubleshooting 3. Installation Instructions 3.1. Remove Old Thermostat 3.2. Installing New Thermostat 3.3. Battery Location 3.4. Wiring and Terminal Functions

Key Specifications

Operation Instructions

Initial Setup

1. Insert Batteries: Install 2 AA alkaline batteries in the rear compartment. Replace when the battery indicator shows low (approximately every 2 years).
2. Power On: If hardwired, ensure 20-30 VAC is supplied via the C terminal. The display should show the home screen.
3. Configure System:

Operating the Thermostat

1. Select Mode: Press SYSTEM to choose HEAT, COOL, AUTO, or OFF.
2. Adjust Temperature: Press up/down arrows to set the desired temperature.
3. Fan Control: Press FAN to select AUTO (runs with heating/cooling) or ON (continuous).
4. Verify Operation:

Temperature Display Adjustment

1. Press MENU to access USER MENU.
2. Use NEXT to navigate to Thermometer Adjustment (item 07).
3. Press up/down arrows to adjust the displayed temperature by ±5°F to match the actual room temperature.
4. Press RUN to save and exit.
Note: Use a separate thermometer for calibration. Relocate the thermostat if near drafts or heat sources.

Troubleshooting

Installation Instructions

Warning: Thermostat installation and all components shall conform to Class II circuits per the NEC code.

Remove Old Thermostat

Installing New Thermostat

  1. Pull the thermostat body off the base. Do not force or pry to avoid damage.
  2. Place base over the hole in the wall and mark mounting hole locations using the base as a template.
  3. Move base out of the way and drill mounting holes. Use plastic screw anchors if needed.
  4. Fasten base snugly to the wall using mounting holes and two screws. Leveling is for appearance only.
  5. Connect wires to the terminal block using the appropriate wiring schematic (see Wiring section).
  6. Push excess wire into the wall and plug the hole with fire-resistant material (e.g., fiberglass insulation) to prevent drafts.
  7. Snap the thermostat onto the base carefully.

Battery Location

Wiring and Terminal Functions

Refer to the equipment manufacturer’s instructions for specific wiring. The following table describes typical terminal functions:

TerminalFunction
RPower (24 VAC)
CCommon wire for 24 VAC power from transformer
WHeat relay
YCompressor contactor (cooling)
GFan relay
O/BHeat pump changeover valve (O: cool, B: heat)

Note: For two-wire heat-only systems (e.g., oil boiler), connect one wire to R and the other to W. Do not exceed specified voltage ratings.

Emerson Thermostat Manual© - All Rights Reserved 2025