Emerson 1F86-0471 Thermostat Operation Manual

The Emerson 1F86-0471 is a Blue 4-Inch non-programmable, single-stage thermostat designed for conventional gas, oil, electric, or heat pump systems without auxiliary heat. It features a large 4-inch backlit display, easy-to-read characters, and automatic heat/cool changeover. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Operating the Thermostat 2.3. Temperature Display Adjustment 2.4. Troubleshooting 3. Installation Instructions 3.1. Remove Old Thermostat 3.2. Installing New Thermostat 3.3. Battery Location 3.4. Wiring and Terminal Functions

Key Specifications

Operation Instructions

Initial Setup

1. Insert Batteries: Install 2 AA alkaline batteries in the rear compartment by pulling the battery door down and lifting it open, following the polarity indicated. Replace when the battery icon shows low (approximately every 2 years). If less than two months of battery life remain, the setpoint may offset by 10°F (cooler in Heat mode, warmer in Cool mode); reset manually with up/down arrows.
2. Power On: If hardwired, ensure 20-30 VAC is supplied via the C terminal. The display should show the home screen with room temperature, setpoint, and battery level.
3. Configure System:

Operating the Thermostat

1. Select Mode: Press SYSTEM to choose HEAT, COOL, AUTO, or OFF.
2. Adjust Temperature: Press up/down arrows to set the desired temperature.
3. Fan Control: Press FAN to select AUTO (runs with heating/cooling) or ON (continuous). Fan AUTO is the most common setting, running only when the system is on.
4. Verify Operation:

Temperature Display Adjustment

1. Access INSTALLER/CONFIGURATION MENU (SYSTEM to OFF, hold MENU for 5 seconds).
2. Navigate to temperature calibration (if available in your model’s menu).
3. Use up/down arrows to adjust the displayed temperature to match the actual room temperature (calibration may be limited to ±4°F in some units).
4. Press RUN to save and exit.
Note: Use a separate thermometer for calibration. Relocate the thermostat if near drafts, heat sources, or exterior walls.

Troubleshooting

Installation Instructions

Warning: Thermostat installation and all components shall conform to Class II circuits per the NEC code. Do not use with line voltage systems; verify wiring with a qualified technician if unsure.

Remove Old Thermostat

Installing New Thermostat

  1. Gently pull the thermostat cover off the base. Do not force or pry to avoid damage.
  2. Place base over the hole in the wall and mark mounting hole locations using the base as a template.
  3. Move base out of the way and drill mounting holes. Use plastic screw anchors if existing holes are too large.
  4. Fasten base snugly to the wall using two mounting screws. Leveling is for appearance only and does not affect operation.
  5. Connect wires to the terminal block using the appropriate wiring schematic (see Wiring section). Use push-connect terminals for secure connections.
  6. Push excess wire into the wall and plug the hole with fire-resistant material (e.g., fiberglass insulation) to prevent drafts.
  7. Snap the thermostat onto the base carefully.

Battery Location

Wiring and Terminal Functions

Refer to the equipment manufacturer’s instructions for specific wiring. The following table describes typical terminal functions:

TerminalFunction
RCCooling power (24 VAC)
RHHeating power (24 VAC)
CCommon wire for 24 VAC power from transformer
WHeat relay
YCompressor contactor (cooling)
GFan relay
O/BHeat pump changeover valve (O: cool, B: heat)

Note: For two-wire heat-only systems, connect one wire to RH and the other to W. For single-transformer systems, jumper RC and RH. For heat pumps, set O/B switch to “O” (cool) or “B” (heat) as required by the system. Do not exceed specified voltage ratings. If no C wire is available, the thermostat can operate on battery power alone.

Emerson Thermostat Manual© - All Rights Reserved 2025