Emerson 1F86-344 Thermostat Operation Manual

The Emerson 1F86-344 is a non-programmable, single-stage thermostat designed for conventional gas, oil, electric, or heat pump systems without auxiliary heat. It features a backlit LCD display, simple operation, and precise temperature control. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Operating the Thermostat 2.3. Temperature Display Adjustment 2.4. Troubleshooting 3. Installation Instructions 3.1. Remove Old Thermostat 3.2. Installing New Thermostat 3.3. Battery Location 3.4. Wiring and Terminal Functions

Key Specifications

Operation Instructions

Initial Setup

1. Insert Batteries: Install 2 AA alkaline batteries in the rear compartment, removing the battery tag to activate. Replace when “LO BATTERY” appears (approximately every 2 years).
2. Power On: If hardwired, ensure 20-30 VAC is supplied via the C terminal. The display should show the home screen.
3. Configure System:

Operating the Thermostat

1. Select Mode: Press SYSTEM to choose HEAT, COOL, AUTO, or OFF.
2. Adjust Temperature: Press up/down arrows to set the desired temperature.
3. Fan Control: Press FAN to select AUTO (runs with heating/cooling) or ON (continuous).
4. Verify Operation:

Temperature Display Adjustment

1. Access CONFIGURATION MENU (SYSTEM to OFF, hold up/down arrows for 5 seconds).
2. Navigate to Item 6 (Temperature Display Adjustment).
3. Use up/down arrows to adjust the displayed temperature by ±4°F to match the actual room temperature.
4. Press RUN to save and exit.
Note: Use a separate thermometer for calibration. Relocate the thermostat if near drafts, heat sources, or exterior walls.

Troubleshooting

Installation Instructions

Warning: Thermostat installation and all components shall conform to Class II circuits per the NEC code. Do not use with line voltage systems; verify wiring with a qualified technician if unsure.

Remove Old Thermostat

Installing New Thermostat

  1. Gently pull the thermostat cover off the base. Do not force or pry to avoid damage.
  2. Place base over the hole in the wall and mark mounting hole locations using the base as a template.
  3. Move base out of the way and drill mounting holes. Use plastic screw anchors if existing holes are too large.
  4. Fasten base snugly to the wall using two mounting screws. Leveling is for appearance only and does not affect operation.
  5. Connect wires to the terminal block using the appropriate wiring schematic (see Wiring section).
  6. Push excess wire into the wall and plug the hole with fire-resistant material (e.g., fiberglass insulation) to prevent drafts.
  7. Snap the thermostat onto the base carefully.

Battery Location

Wiring and Terminal Functions

Refer to the equipment manufacturer’s instructions for specific wiring. The following table describes typical terminal functions:

TerminalFunction
RCCooling power (24 VAC)
RHHeating power (24 VAC)
CCommon wire for 24 VAC power from transformer
WHeat relay
YCompressor contactor (cooling)
GFan relay
O/BHeat pump changeover valve (O: cool, B: heat)

Note: For two-wire heat-only systems, connect one wire to RH and the other to W. For single-transformer systems, jumper RC and RH. For heat pumps, set O/B switch to “O” (cool) or “B” (heat) as required by the system. Do not exceed specified voltage ratings.

Emerson Thermostat Manual© - All Rights Reserved 2025