Emerson 1F95-1291 Thermostat Operation Manual

The Emerson 1F95-1291 is a Big Blue Humidity Universal Thermostat designed for single-stage, multi-stage, or heat pump systems, offering programmable (7-day, 5+1+1 day) or non-programmable modes. It features a 12-inch touchscreen display, humidity/dehumidification control, and automatic heat/cool changeover. Below are the key specifications and operation instructions.

1. Key Specifications 2. Operation Instructions 2.1. Initial Setup 2.2. Setting the Clock and Day 2.3. Operating in Non-Programmable Mode 2.4. Operating in Programmable Mode 2.5. Advanced Features 2.6. Troubleshooting 3. Installation Instructions 3.1. Remove Old Thermostat 3.2. Installing New Thermostat 3.3. Battery Location 3.4. Power Stealing Switches

Key Specifications

Operation Instructions

Initial Setup

1. Insert Batteries: Install 2 AA alkaline batteries in the rear compartment, removing the battery tag to activate. Replace when the battery indicator shows low (approximately every 2 years). If the home is unoccupied for over 3 months and the battery level is low, replace batteries before leaving.
2. Power On: If hardwired, ensure 20-30 VAC is supplied via the C terminal. The touchscreen should display the home screen with room temperature, setpoint, and humidity.
3. Configure System:

Setting the Clock and Day

1. Press MENU, then select SET TIME.
2. Use up/down arrows to adjust hours, minutes, and AM/PM.
3. Select SET DAY and adjust to the current day of the week.
4. Press RUN SCHED to save and exit.

Operating in Non-Programmable Mode

1. Select Mode: Press SYSTEM to choose HEAT, COOL, AUTO, EMER (for heat pumps), or OFF.
2. Adjust Temperature: Press up/down arrows to set the desired temperature.
3. Fan Control: Press FAN to select AUTO (runs only when heating/cooling) or ON (continuous).
4. Manual Override: Press HOLD and adjust temperature to bypass any schedule until RUN SCHED is pressed.

Operating in Programmable Mode

1. Factory Schedule: The thermostat is pre-programmed with energy-saving settings (e.g., Heat: 70°F day, 62°F night; Cool: 78°F day, 82°F night). Press RUN SCHED to use defaults.
2. Custom Schedule:

3. Temporary Override: Press up/down arrows to adjust temperature temporarily until the next period.
4. Permanent Hold: Press HOLD and adjust temperature to maintain it until RUN SCHED is pressed.
5. Disable Programming: Press MENU, hold INSTALLER CONFIG for 5 seconds, and set programming to P0 (non-programmable).

Advanced Features

1. Humidity Control: Configure humidification/dehumidification in INSTALLER CONFIG menu (HM for humidification, DHM for dehumidification). Press the humidity button, then up/down arrows to set desired humidity percentage (5-50% for humidification, 40-95% for dehumidification). In AC mode, if humidity exceeds setpoint, cooling runs to lower humidity, possibly dropping temperature below setpoint.
2. Dual Fuel: With an outdoor sensor, set dual fuel balance point (dF 01-09) in INSTALLER CONFIG to optimize heat pump and fossil fuel operation.
3. Keypad Lockout: Enable in INSTALLER CONFIG with a 3-digit code (000-999); unlock by pressing MENU and RUN SCHED simultaneously for 5 seconds, entering the code.
4. Comfort Alert: If connected to a Comfort Alert module, displays fault codes for compressor issues, flashing “Call For Service” on the screen.
5. Remote Sensors: Supports indoor/outdoor sensors for weighted temperature averaging (configured in INSTALLER CONFIG).
6. Continuous Display Lighting: Enable in INSTALLER CONFIG (requires C wire) for constant backlight in low-light conditions.

Troubleshooting

Installation Instructions

Warning: Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code. To prevent electrical shock or equipment damage, disconnect power at the main fuse or circuit breaker before installation.

Remove Old Thermostat

Installing New Thermostat

  1. Pull the thermostat body off the thermostat base. Do not force or pry to avoid damage.
  2. Place base over the hole in the wall and mark mounting hole locations using the base as a template.
  3. Move base out of the way, drill mounting holes. Use plastic screw anchors if existing holes are too large.
  4. Fasten base snugly to the wall using mounting holes and two mounting screws. Leveling is for appearance only and does not affect operation.
  5. Connect wires to the terminal block on the base using the appropriate wiring schematic (refer to equipment manufacturer’s instructions).
  6. Push excess wire into the wall and plug the hole with fire-resistant material (e.g., fiberglass insulation) to prevent drafts.
  7. Carefully line the thermostat up with the base and snap into place.

Battery Location

Power Stealing Switches

Leave switches in the “On” position for most systems. Details in the following table:

Thermostat Power MethodSwitch Position/Description
Battery Powered, no 24 Volt systemSwitches “On”, thermostat runs on batteries.
Hardwired with Battery Back-up, for 24 Volt systems with common connection from transformer to “C” terminalSwitches “On”, thermostat runs on power directly from transformer with battery back-up.
Battery Powered with Power Stealing Assist, for 24 Volt systems with no common connectionSwitches “On”, thermostat runs on batteries and supplemental power drawn through heat or cool circuit.

Caution: Power Stealing Assist may cause issues on systems with high impedance electronic modules (e.g., furnace draft inducer motor running with no call for heat, furnace fan not turning off). If the air conditioner does not turn off when cooling demand ends, set switches to “Off” to operate on batteries, correcting the condition.

Emerson Thermostat Manual© - All Rights Reserved 2025